BACnet/IP

BACnet over IP; ASHRAE 135

BACnet/IP is the Ethernet and UDP implementation of ASHRAE Standard 135 (ISO 16484-5), the open, vendor-neutral protocol that dominates building automation. Lighting systems expose objects such as occupancy and energy over UDP port 47808, with BTL listing as the conformance proof.

What it is

BACnet/IP is the version of the BACnet building automation protocol (ASHRAE Standard 135, also published as ISO 16484-5) that runs over Ethernet and IP networks, using UDP port 47808 by default. It lets equipment from different manufacturers share data and commands through standard objects, such as occupancy, light level and energy.

Look for devices listed by BACnet Testing Laboratories (BTL), which have been tested for conformance. Even with listed devices, each integration should be validated on the project; compatibility is not automatic.

Standard BACnet/IP has no built-in authentication or encryption, so protect it with network segmentation, or use BACnet/SC where security matters.